MTS FlexTest® Models 40/60/100/200 Controller Hardware
Model 493.80 Encoder Interface Board
Digital I/O and Transition Boards
258
Power Settings for the Model 493.80 Encoder Interface Board
Power for the encoders can be supplied from the Model 493.80 board. Three
voltage levels (+5 V DC, +/- 15 V DC, and +24 V DC) are available and can
be selected by the jumper settings in the following table.
Note It is the system integrator’s responsibility to determine the suitability
(cable line loss, current requirements) of the internal power
configuration.
For more information For jumper locations, see “Jumper Settings and Locations for the Model
493.80 Encoder Interface Board” on page 259.
Power Settings for the Model 493.80 Encoder Interface Board
C
HANNEL +5 V DC +/- 15 V DC + 24 V DC
1X3 (No jumper)
X4 (1-2)
X5 (1-2)
X6 (No jumper)
X3 (1-2)
X4 (1-2)
X5 (2-3)
X6 (1-2)
X3 (No jumper)
X4 (2-3)
X5 (2-3)
X6 (2-3)
2X7 (No jumper)
X8 (1-2)
X9 (1-2)
X10 (No jumper)
X7 (1-2)
X8 (1-2)
X9 (2-3)
X10 (1-2)
X7 (No jumper)
X8 (2-3)
X9 (2-3)
X10 (2-3)
3X11 (No jumper)
X12 (1-2)
X13 (1-2)
X14 (No jumper)
X11 (1-2)
X12 (1-2)
X13 (2-3)
X14 (1-2)
X11 (No jumper)
X12 (2-3)
X13 (2-3)
X14 (2-3)
4X15 (No jumper)
X16 (1-2)
X17 (1-2)
X18 (No jumper)
X15 (1-2)
X16 (1-2)
X17 (2-3)
X18 (1-2)
X15 (No jumper)
X16 (2-3)
X17 (2-3)
X18 (2-3)